FREQUENTLY
ASKED QUESTIONS AND ANSWERS-ETO
Q. What is a phase?
Phase in A.C system is the fraction of time period
which has elapsed since current/voltage last passed through zero position of
reference. The unit is in secs or
radians.
Q. What is the difference between shock received
due to DC and that due to AC?
Current from a steady DC
source in passing through the skin will tend to cause muscular contraction at
the initial contact and when the contact is broken. AC produces a continuing
spasm in the muscles through which current passes, with its change from forward
to reverse flow either at 50 Hz or 60 Hz rate.
AC has the ability to stimulate nerves directly.
Q. How will you check a diode
with multimeter?
Remove or disconnect the diode
from the circuit. ( If the power is
turned off instead of disconnecting the diode, discharge all capacitors and
remove all fuses in the circuit). Multimeter drives a small DC current (a few mA) through the diode P-N junction and
acts as a voltmeter to measure the voltage across it. Connect the two probes across the diode. Read the voltage drop, it should be 0.5V –
0.8V (500 mV to 800 mV) for a healthy
silicon diode. Reverse the probe
connections and the display should indicate ‘over-range’. If the display indicates over the range in both
directions, means the diode is open-circuited.
If the display indicates less than 1V in both directions, the diode maybe
short-circuited.
Q. Why does a motor rotate?
DC Motor: when the field is excited and the armature is
supplied with current from supply mains, they experience a force tending to
rotate armature (direction given by Fleming’s left-hand rule). Each conductor experiences a force and all
these forces collectively produce a driving torque which sets armature
rotating.
Induction motor: Rotor does not receive electric power from
supply, but by induction from the stator.
When 3 phase stator windings are fed by a 3 phase supply, a magnetic
flux of constant magnitude, rotating at synchronous speed is set up. The flux passes through the air gap, sweeps
past the rotor surface and so cuts the rotor conductors which are as yet
stationary. Due to relative speed between the rotating flux and the stationary
conductors, an emf is induced in the rotor. The frequency of this induced emf is
the same as supply frequency. Magnitude
is proportional to the relative velocity between flux and conductors (Fleming’s
right-hand rule). Due to this emf rotor current is produced
(rotor conductors form a closed circuit), whose direction (Lenz’s slaw) is such
as to oppose the very cause producing it.
In this case, the cause which produces the rotor current is the relative
velocity between the rotating flux of the stator and the stationary rotor
conductors. Hence to reduce the relative
velocity, the rotor starts running in the same direction as that of flux and tries
to catch up with the rotating flux.
Q. What are the functions of choke in the tube
light circuit?
To provide starting
voltage and to maintain the p.d across
the tube ( when main supply is AC)
When the supply is DC, the ballast resistor is used.
Q. What is an electric shock?
Electric shock is due to the flow of current through the body. This is often from hand to hand or hand to
foot. A shock current of 15mA AC or DC may be fatal.
Q. What are the conditions that affect the
electric shock?
The size of the electric shock current is related to the following
factors: 1. Applied voltage (2)
Body resistance. The size of
human body resistance depends on other factors also, like the state of health,
degree of contact with live wires, perspiration or dampness of skin. Typical dry full contact body resistance is
about 5000Ω at 25V, falling to about 2000Ω at 250V. This indicates that human body resistance
goes down as the applied voltage goes up, giving rise to the increased current
at high voltages.
Q. What are the types of switchboards available?
Switchboards may be open type in which all essential switchgear is
exposed on the front of the panel or ‘dead front’ type in which all the live
parts are concealed behind sheet steel panels.
Only the operating handles and instruments appear on the front. While DC switchboards may employ an open type
panels, the ‘dead front’ type is mandatory on the AC system.
Q. Which system of supply is more lethal, AC or
DC?
AC supply is more lethal than DC supply at similar voltages. On no account should work of even the simplest nature be undertaken on live AC apparatus without the operator being
fully protected.
Q. What are the precautions to be observed
before commencing work on a switchboard?
Before any work is done on the electrical equipment, follow the
following safety procedures:
1.there should be an approved rubber matting on the floor, in front of
the switchboard, for safety.
2. Rubber gloves should be
specially made for the purpose and comply with regulatory requirements.
3. portable hand lamps if used
should be fully insulated without metal guards so that there is no risk of
shock or short circuits.
4. Precautions must be observed to isolate and lock off the
apparatus. Where fuses are provided,
these should also be removed.
5. Where pilot lights, control
circuits are concerned, these may still have power from separate sources, even
though the main power circuit may be isolated.
6. If the draw-out type circuit
breaker is being overhauled, it will become dead, when it is pulled out fully.
7. Before commencing work, it
should be verified that the apparatus is actually dead using a live line
tester. This test should be conducted
between phases, and also between phase and earth.
8. A warning sign to be posted
indicating the work is progressing in the apparatus.
9. A switchboard can not be
considered dead unless all generators connected to it are off and all other
supplies disconnected.
Q. What do you understand by the term ‘dead
switchboard’?
A dead switchboard is the one in which there is no supply of power
available, whatsoever.
Q. What is the setting of the reverse power relay?
-10% of generator [power rating with 5 secs time delay for diesel-driven
alternator.
-2 to -5% of generator power rating with 5 secs time delay for turbo
alternator.
Q. What is understood by the term ‘Insulation
Resistance’?
Insulation resistance is a measure of opposition offered to the current
by the insulating materials
Q. What
are the factors that affect insulation resistance?
Insulation is affected by many factors such as:
1 Moisture – results in a decrease in the measured value of insulation resistance.
2. Dust and dirt
deposits - reduces insulation resistance and failure of
insulation due to oxidation.
3. Oil and
grease -
prevents heat dissipation and cause dust and dirt to settle on the
insulation thereby reduces insulation resistance and leads to failure.
4. Aging - over a period of time the insulation
deteriorates due to it getting affected
by temperature variation, mechanical stresses, vibrations, moisture,
dirt deposits, chemical contacts, etc
Some varnishes tend to become hard with age and crack during the
operation.
5. Temperature -
excessive temperature dehydrates and oxidizes the insulation, making it
brittle and disintegrate under vibration and shock.
Q. What is understood by the term ‘permissible
temperature rise’ in case of insulation?
Permissible temperature rise is the difference between the ambient
temperature and maximum permitted temperature for the class of insulation in
use.
Q. What is the relationship between the
insulation and the temperature?
The insulation resistance falls with temperature rise. Life of insulation will be halved for every
10ºC above the permitted temperature.
For example, a machine designed for continuous operation at 70ºC will
have its useful life cut in half when operating at 80ºC.
Q. Why the insulation tests are carried out on
electrical equipment?
A measurement of the insulation resistance gives the best guide to the
state of health of the electrical equipment.
The marine environment is particularly arduous for electrical equipment,
due to damp salt-laden atmospheres, extreme temperatures, and vibrations. The continuous operation of equipment onboard ship demands high operating efficiency and optimum economy in order to
keep down costs.
Q. What is the most preferred condition for
measuring insulation resistance?
Insulation resistance becomes leakier at high temperatures. So the insulation test should be done while the
machine is hot just after it has stopped.
This will give a realistic reading at near working temperature.
Q. What is ‘megger’?
The instrument used for measuring insulation resistance in Mega Ohms.
Q. What is armoring in a cable?
Extra mechanical protection provided by armoring with woven wire braid made of galvanized
steel or tinned phosphor bronze. Steel
armoring is not preferred for single-core cables carrying heavy alternating
currents because of magnetic properties.
Q. What is meant by the current rating of a cable?
The passage of current through a cable conductor results in the rise of
temperature due to resistance of the conductor.
Therefore maximum current rating is based upon maximum operating the temperature of the insulation and sheathing.
Q. What is the short circuit rating?
Under short circuit conditions, there is a rapid rise in the conductor
temperature, affecting cable insulation.
Mechanical forces due to magnetic effect and longitudinal expansion of
conductors due to heat have also to be considered. It is, therefore, necessary to match the cable
size with the short circuit protection equipment (fuses or circuit breakers)
which may take a certain time (a fraction of a second to several seconds ) to
trip.
Q. What are the factors that are to comply
by the installed cables?
The cables installed must comply with Current ratings and Voltage drop
limitations. Passage of current results
in a voltage drop along the length of the cables,. Hence the voltage drop becomes a problem in very
long cables. Excessive voltage drop can
seriously affect the proper operation of electronic equipment. Motors can give starting problems if voltage
drop at the starting current is excessive.
The voltage drop in cables from the main switchboard to the appliance
must not exceed 6% (practice it is
about 2%)
Q. Comment on the requirements of conduits in
regard to cable installation
- Cable
outlets from conduits should be bushed to prevent abrasion at the ends.
- Total the cross-sectional area of cables should be less than 40% of the cross
section area on the conduit.
- Ventilation
of conduits should be provided, and it should be ensured that water does not
collect in the conduit.
- The
conduit should be earthed.
Q. How the cables are grouped or ‘bunched’?
1. When several cables are run
close together or are touching, the heat from one cable affects others and
thus requires a lowering the rating. For
example, if more than 6 cables are running bunched together, it is usual to
reduce the current ratings to 85%.
2. Where possible, cables
intended for different operating temperatures should not be bunched in common
clips, glands, conduits or pipes.
Q. What are the sources of electrical power on
ship?
- Main alternator
- Emergency generator
- Emergency batteries
- Shore power
Q. What are the functions of circuit breakers,
fuses relays?
The circuit breakers and switches are the means of controlling the flow
of electric current. The fuses and the
relays protect the distribution system from large fault currents.
Q. What is understood by ‘essential loads’?
Essential loads or services are those required for the safety of
personnel and for safe navigation and propulsion of the ship.
Q. Why the emergency source of electrical power is
provided?
Emergency source of the power supply is provided so that in the event of an
total power failure, supply will still be available for emergency lighting,
alarms, communications, watertight doors and services necessary to maintain
safety.
Q. Comment on the sequence of events following a
mains failure?
Control and monitoring equipment of emergency generator on sensing a
large drop in voltage or frequency sends a starting signal to an emergency
generator. Bus tie-breaker between the
main switchboard and emergency switchboard opens. In 45 secs the emergency generator starts and
comes on load. During this time the
supply for emergency lighting, alarm, etc are maintained by the emergency
batteries. In case an emergency generator
fails to come on load, these batteries can supply power to selected lighting,
communication and alarm circuits for a minimum period of half an hour.
Q. How the emergency power supply is tested?
The correct functioning of the auto start equipment is obviously vital to
the production of emergency power.
Regular, weekly testing of the emergency generator should include
simulation of the loss of normal power.
The start-up equipment may provide a push-button to interrupt the normal
voltage supply to the panel which then triggers the start sequence. Loss of main power supply can easily be
simulated by pulling a fuse in the auto start panel which supplies the under-voltage or under frequency relay.
Emergency generators should be regularly checked and run up for short
test runs to comply with safety regulations.
These no-load running checks should, when practicable, be supplemented
occasionally by a proper load test. This
requires the disconnection of normal mains power while the emergency generator
is loaded up to near its rated value.
Only a proper load test will prove the performance of the generator and its
prime mover, together with the circuit breaker operation.
Q. What is the reason for using insulated the neutral system in ships?
The priority requirement on board ship is to maintain continuity of the
electrical supply to equipment in the event of a single earth fault occurring.
Q. What are the causes of the short circuit?
A short circuit may occur because of the breakdown of the insulation of equipment due to overheating or ingress of water. Sometimes terminal connections become loose,
causing two power supply cables to make electrical contact. A short circuit may also occur in the windings
of a transformer because of insulation breakdown due to overheating. Electrical cables exposed to fire, mechanical
damage, cuts, etc. can cause a short circuit.
Q. Why the equipments are earthed on board the
ship?
In order to protect against the dangers of electric shock and fire that
may result from earth faults, the metal enclosures and other non-current
carrying metal parts of electrical equipment must be earthed. The earthing conductor connects the metal
enclosures to earth (ship’s hull) and prevents such metal parts from attaining
dangerous voltage with respect to earth in the event of an earth fault
occurring.
Q. What are the common locations of earth faults
?
Earth faults are found at lamp fittings and terminals etc., where
moisture has found its way in.
1. Lamp fittings on the open deck, exposed to rough
weather is prone to ingress of
moisture.
2. In accommodation, washing machines drenched with
water area another source of earth faults.
3. In the galley, the ovens, hot plates, etc., are also
exposed to earth faults.
4. Dripping water over electrical machinery.
5. Motors standing idle for a long time - their
insulation gets affected by condensed moisture.
6. Overheated insulations of motor and cables cause
drop in insulation resistance.
7. Dirty electrical apparatus with surface
tracking (leaking current)
8. Old electrical apparatus whose insulation has
aged has become brittle.
9. The terminal wire which has become loose from the
terminal and is touching the metal casing of electrical machinery.
Q. How the earth faults are treated?
Earth faults should be eliminated when located. Damaged conductor insulation must be repaired
the method of repairing depends on the cause of earth's fault and this is
determined by visual examination. A lamp
fitting that is damaged must be replaced.
Dampness or moisture in insulation must be dried out by gentle heat and
then precautions taken to prevent future ingress of moisture. Insulation that has been mechanically damaged
or damaged by overheating must be made good again. If surface dirt is the cause, a thorough
cleaning with an electro cleaner solvent will probably cure the fault.
Q. What is the rating of a fuse?
The fuse rating is the current fuse will carry continuously and it is
important that rating is correct for the normal current flowing in the circuit
it protects.
Q. What are the reasons for installing fault
protection in the electrical distribution system?
1. To disconnect and isolate
faulty equipment in order to maintain the power supply to the remaining healthy
circuits in the system.
2. To prevent damage to
equipment from thermal and magnetic forces that occur during short circuit and
overload faults.
3. To protect personnel from
electric shock.
Q. How is the strength of circuit breaker or
fuse is specified?
By its breaking capacity, which is the maximum fault current it can
safely interrupt.
Q. Why HRC fuses are normally preferred for
Electrical installations on board ship?
- Time/current
fusing characteristics are very consistent.
- HRC
fuses are reliable and non deteriorating in service
- Fuses
have very high breaking capacity.
- They
also have a very high speed of operation at high short circuit fault,
faster than a circuit breaker.
Q. How a fuse is selected for circuit protection
?
- Rating of fuse for
LIGHTING or HEATING circuit: it is the current which a fuse will carry continuously. For a 50A circuit, a 50A fuse would be appropriate, unless it was a motor circuit.
- Rating of fuse for
MOTOR circuit: In motor circuits, the fuse should be large enough to carry starting current for the time necessary to start the motor plus necessary margin. For motor,
fuses are typically rated at 2-3 times mot full load.
Q. How the overload protection device is tested
and set?
Overload relays and circuit breakers should be tested
periodically. Bimetal elements in
thermal overload relays become insensitive to heat from metal fatigue and fail
to operate under overload conditions.
These relays should be checked for corrosion, accumulation of dirt and
other foreign matters that blocks the free movement of the tripping element.
Overcurrent relays and circuit breakers may be tested by passing a
specified overcurrent through the heater or overload coil and observing the time required for it to trip. The actual
tripping time should then be compared with the manufacturer’s current time
characteristics.
Test an overload rely on, it should be disconnected from the power line
and connected to low voltage, high current power source like variable
autotransformer. The current is adjusted to
test value by connecting to one of the bimetal heaters via heavy test
leads. A stopwatch is used to determine
tripping time.
Magnetic overload trips and circuit breakers may be tested in similar
manner.
Q. What is under-voltage protection for
Generator and Motor?
An under-voltage release is fitted to all generator’s circuit
breaker. Its main function is to trip
the circuit breaker when severe voltage dip occurs. The under-voltage release on a generator
circuit breaker also prevents it from being closed when the generator voltage is
very low or absent. The under voltage
relay prevents the closure of the circuit breaker of the dead generator.
Under-voltage protection is also required for motor starters. The starter contactor normally provides this
protection as it drops out when the supply voltage is lost or is drastically
reduced. The starter circuit will not
normally allow the motor to restart when the voltage supply is restored, except
when special automatic restarting facilities are provided. This ensures that when the supply returns
after a blackout, all the motors do not start together, thereby tripping the
generator circuit breaker again..
Essential motors may be arranged to start automatically by sequential
start with staggered time delays.
Q. How the under voltage relay is checked and
calibrated?
Under-voltage protection can be electronic or electromagnetic. checking and calibration of generators’ under
voltage relays can only be done accurately by voltage injection. A known variable voltage is directly applied
to the under-voltage relay to check :
1. the voltage at which relay
pulls in (2) the voltage at which relay drops out. Generator under voltage relays has a time
delay to prevent false tripping during transient voltage dips (typically 15%),
caused by large motor starting currents.
Q. How does current flow in the shaft of an
generator?
Machines with a very strong magnetic field often generate a voltage in
the shaft that causes a current flow through bearings.
Q. What are the effects of shaft current in a
generator?
The flow of electric current through the bearings causes electrolytic
action, which will cause bearing failure in due course and possible sludging of
lubricating oil.
Q. How the shaft currents are prevented?
To eliminate shaft currents either (a) outboard bearing shell is
insulated in the housing, or (b) outboard bearing pedestal is insulated from
the foundation.
All lub oil pipe connections that make connection with the shaft or the
particular bearing must also be insulated.
Q. Why both bearings are not insulated?
Insulating both bearings would permit the build-up of electrical
charges (static electricity). The
resulting high voltage will be dangerous to operate personnel.
Q. How the insulation of pedestal bearing
checked?
2. Condition of insulation can also be checked
while the machine is running by measuring milli-volts between the shaft and the
bedplate. Two readings are taken, one
with the jumper connecting the shaft to the pedestal and one without the jumper. If insulation is good, both readings will be
alike. If the insulation is defective,
the reading in (1) will be higher than in (2).
Q. How is the insulation resistance of
alternator checked?
Disconnect any electronic circuit components which may be damaged by a
500V insulation test. Consult the wiring
diagrams and manufacturer’s instructions before testing. Measure the insulation of the stator winding
and the rotor windings to earth, and between stator phases. The minimum value is 1MΩ, but a lower value may be acceptable to surveyor based on 1kΩ/volt, e.g. 450
kΩ for a 450-volt generator.
Q. What is the purpose of shading coil in a
contactor?
To reduce vibration, chattering and
noise.
Q. What is the purpose of ICCP? (impressed current cathodic protection)
To prevent corrosion of the hull, propeller, rudder and line shafting
Q. What is the supply given to the shipboard general
alarm?
24V DC.
Q. When a component is to be removed from a PCB,
what precaution will be taken?
Before soldering, the component a tightly knit metal braid wire will
be used.
Q. Armature coils are tested with a low voltage
source. What will be the indication for
short-circuited coils?
For short-circuited coils, the voltmeter reading will show low or zero,
other coils will have higher readings.
Q. What do you understand by the term ‘varnished
cambric’?
This is an insulating material made of cotton cloth dipped (or coated)
with an insulating varnish.
Q. What is understood by ‘dead front’
switchboard?
Dead front switchboard is one with insulated switches and no exposed
terminals.
The voltage and current developed in an AC circuit reach their peak
values at the same time.
The voltage and current are said to be in phase when the power factor is
unity.
Q. Under what circumstances would semi-conductor (or high-speed fuses) be
used on a soft starter application? What purpose do they serve?
Semiconductor fuses are an energy limiting fuse using specially shaped
silver elements in a silicon sand environment. Because of their energy limiting
characteristics, they are able to protect semiconductor devices from excess
energy let through under fault current conditions.
A soft starter uses reverse parallel connected SCRs or thyristors in series with the supply to the motor. If a short circuit occurs between the starter and the motor, or in the motor itself, there is no limiting impedance to restrict the current flow and so the current is essentially the short circuit current of the supply. In most cases, this is enough to damage or destroy the SCRs. It is not practical to turn an SCR off once the current has begun to flow, so electronic protection is not practical. Current will stop at the next zero crossings which could be half a cycle later. The semiconductor fuse is able to interrupt the current flow in less than half a cycle, and the rupture time is dependant on the total energy flow.
SCRs have a maximum short term energy rating that is usually called I squared t (Current squared times time) and provided the maximum let through I2t (or total clearing I2t) of the fuse at the operating voltage of the supply, is less than the I2t of the SCRs, then the fuse should fail before the SCRs.
Semiconductor fuses can be a bit of a problem at times because their pre arcing I2t is well below their total clearing I2t and they can be stressed by the normal operation of the starter and fail prematurely. It is important to compare the overload time-current curve of the fuse with the operation of the starter.
A soft starter uses reverse parallel connected SCRs or thyristors in series with the supply to the motor. If a short circuit occurs between the starter and the motor, or in the motor itself, there is no limiting impedance to restrict the current flow and so the current is essentially the short circuit current of the supply. In most cases, this is enough to damage or destroy the SCRs. It is not practical to turn an SCR off once the current has begun to flow, so electronic protection is not practical. Current will stop at the next zero crossings which could be half a cycle later. The semiconductor fuse is able to interrupt the current flow in less than half a cycle, and the rupture time is dependant on the total energy flow.
SCRs have a maximum short term energy rating that is usually called I squared t (Current squared times time) and provided the maximum let through I2t (or total clearing I2t) of the fuse at the operating voltage of the supply, is less than the I2t of the SCRs, then the fuse should fail before the SCRs.
Semiconductor fuses can be a bit of a problem at times because their pre arcing I2t is well below their total clearing I2t and they can be stressed by the normal operation of the starter and fail prematurely. It is important to compare the overload time-current curve of the fuse with the operation of the starter.
Q. What are the guidelines
for understanding the specific rating of the DG Sets?
STANDBY POWER RATING:
Applicable for supplying emergency power for the duration of the utility power
outage. No overload capacity is available for this rating. Under no condition
is an engine allowed to operate in parallel with the public utility at the
Standby Power Rating. This rating should be applied where reliable utility power
is available. A Standby rated engine should be sized for a maximum of an 80%
average load factor and 200 hours of operation per year. This includes less
than 25 hours per year at the Standby Power Rating. Standby Ratings should
never be applied except in true emergency power outage. Negotiated power outages
contracted with a utility company are not considered an emergency.
PRIME POWER RATING:
Applicable for supplying electric power in lieu of commercially purchased
power. Prime Power Applications must be in the form of one of the following two
categories:
UNLIMITED TIME RUNNING PRIME POWER:
Prime power is
available for an unlimited number of hours per year in a variable load
application.
Variable load
should not exceed a 70% average of the Prime Power rating during any operation
period of 250 hours.
The total operating
time at 100% Prime Power shall not exceed 500 hours per year.
A 10% overload
capability is available for a period of 1 hour within a 12 hour period of
operation.
Total
operating time at the 10% overload power shall not exceed 25 hours per year.
LIMITED TIME RUNNING PRIME POWER:
Limited time Prime
Power is available for a limited number of hours in a non-variable load
application. It is intended for use in a situation where power outages
are contracted, such as utility power
curtailment.
Engines may be
operated in parallel to the public utility up to 750 hours per year at power
levels never to exceed the Prime Power Rating.
The customer should
be aware, however, that the life of any engine will be reduced by this constant
high load operation. Any operation exceeding 750 hours
per year at the Limited-time, Prime Power rating should use the
Continuous Power Rating.
CONTINUOUS POWER RATING: Applicable for supplying utility power at a
constant 100% load for an unlimited number of hours per year. No overload
capability is available for this rating.
SPACE HEATER
Small resistance heater units mounted in a motor, that are energized, during the motor shutdown, to
prevent condensation of moisture on the motor windings.
INDUCTION MOTORS:
Q. What is slip?
SLIP
The difference between the speed of the rotating magnetic field (which is
always synchronous) and the rotor in a non-synchronous induction motor is known
as slip and is expressed as a percentage of synchronous speed. Slip generally
increases with an increase in torque.
Q. What happens if
a motor is operated in Star instead of Delta?
If the motor is designed to be operated in the delta on your local supply
voltage, then operating continuously in star can cause damage to the motor.
When a delta motor is connected in star, the voltage across the windings is
reduced by the square root of three resulting in reduced flux in the iron. This
will reduce the magnetizing current, and will also reduce the torque capacity
of the motor. If you operate at light loads, there will be no problem, however, if you operate at high loads, the slip of the motor will be increased
dramatically and it may stall. The increased slip will result in a dramatic
increase in the power dissipated in the rotor. If the motor begins to stall,
the stator will also suffer excess heating causing motor failure.
Q. Can I run a 60Hz rated the motor on 50Hz?
Induction motors use an iron core and require flux in the iron to
operate. In order to achieve the commercial goals of the smallest size and lowest
price at the best efficiency, induction motors are designed to operate at a high
level of flux in the iron. The flux is determined by the turns, voltage, and frequency.
In a modern motor, if the flux is increased by a small amount, the iron losses
increase and the iron tends towards saturation. At saturation, the inductance
begins to fall and the current increases further. To reduce the flux at a given
voltage and frequency, the turns on the stator are increased. This reduces the
Iron loss, but a longer length of thinner wire is used and the copper loss
increases. Design becomes a balancing act between copper loss and iron loss and
so the design is optimized for a given voltage and frequency.
If the voltage applied to the motor is held constant and the frequency
is increased, the inductive reactance increases and so the flux reduces. This
effectively reduces the maximum torque capacity of the motor and so the motor
power rating at the higher frequency remains the same.
If the voltage applied to the motor is held constant and the frequency
is reduced, the current will increase and in theory, the torque will also
increase. The motor should be able to deliver the same power also, BUT the flux
in the iron is now too high resulting in excessive iron loss, and the motor
will fail prematurely. Above a very low frequency, (5 - 10Hz) the impedance of
the magnetizing circuit of the motor is primarily inductive and so in order to
keep the flux within limits, it is important to keep a linear V/F ratio
(Voltage to Frequency ratio). If the frequency is reduced by 10%, the voltage
must also be reduced by 10%. Because the flux in the iron remains the same, the
torque capacity remains the same and so the power rating of the motor also
drops by 10%.
Provided the voltage is dropped by the same proportion as the
frequency, it is OK to run a 60Hz motor on 50Hz. The speed will be reduced by
the reduction in frequency and the power capacity will also reduce by the
reduction in frequency.
60 Hz Volts
|
50 Hz Volts
|
480
|
400
|
460
|
383
|
440
|
367
|
230
|
191
|
Q. How
do you set up a thermal over load? Do you set it for the current drawn or for
the motor rating?
Strictly speaking, you would normally set the overload protection to
the rating of the motor, but if the motor always operates below its rating,
then setting the overload closer to the actual operating current will afford a higher level of protection provided that the motor is still able to start
without tripping the overload.
The method that normally advocated for setting a thermal overload is to
operate the motor at maximum load for an extended period of time, then slowly
adjust the overload down until it trips, then set the relay a small margin
higher. The problem with thermal overloads is that the calibration is coarse, to
say the least, and this method ensures that you have protection against a
change in the load characteristics of the motor condition. If there are occasional
nuisance trips, then the setting can be increased, but should not exceed the
motor rating.
Q. Under what circumstances
would semi-conductor (or high-speed fuses) be used on a soft starter
application? What purpose do they serve?
Semiconductor fuses are an energy limiting fuse using specially shaped
silver elements in a silicon sand environment. Because of their energy limiting
characteristics, they are able to protect semiconductor devices from excess
energy let through under fault current conditions.
A soft starter uses reverse parallel connected SCRs or thyristors in series
with the supply to the motor. If a short circuit occurs between the starter and
the motor, or in the motor itself, there is no limiting impedance to restrict
the current flow and so the current is essentially the short circuit current of
the supply. In most cases, this is enough to damage or destroy the SCRs. It is
not practical to turn an SCR off once the current has begun to flow, so electronic
protection is not practical. Current will stop at the next zero crossings which
could be half a cycle later. The semiconductor fuse is able to interrupt the
current flow in less than half a cycle, and the rupture time is dependant on
the total energy flow.
SCRs have a maximum short term energy rating that is usually called I squared t
(Current squared times time) and provided the maximum let through I2t (or total
clearing I2t) of the fuse at the operating voltage of the supply, is less than
the I2t of the SCRs, then the fuse should fail before the SCRs.
Semiconductor fuses can be a bit of a problem at times because their pre arcing
I2t is well below their total clearing I2t and they can
be stressed by the normal operation of the starter and fail prematurely. It is
important to compare the overload time-current curve of the fuse with the
operation of the starter.
Q. Can I Bridge out the slip
rings and use a soft starter on a slip ring motor?
A slip ring motor uses resistors in the rotor circuit to modify the
starting characteristics of the slip ring motor. Increasing the resistance in
the rotor circuit has two effects:
1. It reduces the start of current
2. It increases the slip at which maximum torque occurs.
If the slip ring motor has been employed to provide a very high
starting torque across the entire speed range during start, then the slip ring
or secondary resistance starter can not be replaced. In this case, the first
stage of the resistors would be selected to provide high torque at 100% slip
(zero speed) and a number of stages are then employed, each with reducing
resistance to moving the Slip point in steps from 100% towards 0%. The effect of
this is to provide maximum torque at all speeds and at a reduced start current.
(typically 200 - 300%)
Shorting out the slip rings and attempting any form of reduced voltage
start in the stator supply, will result in a much-reduced start torque at a
much higher start current. Effectively, the motor could exhibit a Locked Rotor
Current in excess of 1000% and a Locked Rotor Current less than 100%. If we
reduce the start current down to say 400%, then the start torque would be less
than 100 x (400/1000) x (400/1000) or less than 16%!
If the driven load does not require a high start torque, then the slip
ring motor can be set up to emulate a standard cage motor by applying rotor
resistance that will cause a full voltage to start current of about 550%. A
reduced voltage starter can now be applied, and the rings should be shorted out
once the machine reaches full speed. If you do not short the rings at full
speed, the slip will be higher than ideal and the motor efficiency will be
reduced. There will be a high power dissipation in the resistors
Q. What is understood by
service factor?
SERVICE FACTOR
1. When used on a motor nameplate, a number which indicates how much above
the nameplate rating a motor can be loaded without causing serious degradation,
(i.e., a 1.15 S-F can produce 15% greater torque than the 1.0 S-F rating of the same motor).
2. When used in applying motors or gear motors, a figure of merit is used
to "adjust" measured loads in an attempt to compensate for conditions
that are difficult to measure or define. Typically, measured loads are
multiplied by service factors (experience factors) and the result in an
"equivalent required torque" rating of a motor or gear motor.
Q. What is skew?
SKEW
Arrangement of laminations on a rotor or armature to provide a slight angular
pattern of their slots with respect to the shaft axis. This pattern helps to
eliminate low-speed cogging effects in an armature and minimize induced
vibration in a rotor as well as reduce associated noise. It also can help to
increase starting torque.
Q. What is a splash-proof
motor?
SPLASH-PROOF
MOTOR
An open motor in which the ventilating openings are so constructed that
drops of liquid or solid particles falling on it or coming toward it in the straight line at any angle not greater than 100 degrees from the vertical,
cannot enter either directly or by striking and running along a surface of the
motor.
Q. What is understood by
split phase start?
SPLIT PHASE START
The motor employs a main winding and an auxiliary winding, which is called
the starting winding. The windings are unlike and thereby "split" the
single phase of the power supply by causing a phase displacement between the
currents of the two windings thus producing a rotating field. After the motor
has attained approximately 75% of rated speed, the starting winding is
automatically disconnected by means of a centrifugal switch or by a relay. The
motor then continues to run on a single oscillating field, which in conjunction
with the rotation of the rotor, results in a rotating field effect. Since there
is no rotating field, after the starting winding is de-energized, the rotation
cannot be changed until the motor has come to rest or at least slowed down to
the speed at which the automatic switch closes. Special starting switches are
available as well as special reversing switches which have a means for shunting
the open contacts of the automatic switch while the motor is running and thus permits
the split-phase motor to be reversed while rotating. This type of starting is
found typically on single-phase fractional motors.
Q. What are the different types of enclosures
available for induction motors?
1. Totally enclosed, Non ventilated type: Such motors have solid frames and end shields,
but no openings for ventilation.
2.Splash-proof type: In the frames of such motors, the ventilating openings are so constructed that the liquid drops or dust particles falling on the motor will not be able to enter the motor when the incident angle is not greater than 100º.
3. Totally enclosed, fan-cooled type
4. Protected type : end covers have perforated covers.
5.Drip-proof motors: the frames have so constructed that liquid drops or dust particles, falling on the machine at any angle greater than 15º from the vertical, cannot enter the motor, either directly or by striking and running along a horizontal or inwardly inclined smooth surface.
6.Self ventilated type: consists of enclosed shields with provision for pipe connection on both the shields. The motor fan circulates sufficient air through pipes which are of ample section.
7. Separately (forced) ventilated type.
2.Splash-proof type: In the frames of such motors, the ventilating openings are so constructed that the liquid drops or dust particles falling on the motor will not be able to enter the motor when the incident angle is not greater than 100º.
3. Totally enclosed, fan-cooled type
4. Protected type : end covers have perforated covers.
5.Drip-proof motors: the frames have so constructed that liquid drops or dust particles, falling on the machine at any angle greater than 15º from the vertical, cannot enter the motor, either directly or by striking and running along a horizontal or inwardly inclined smooth surface.
6.Self ventilated type: consists of enclosed shields with provision for pipe connection on both the shields. The motor fan circulates sufficient air through pipes which are of ample section.
7. Separately (forced) ventilated type.
Q. How to do changes in supply voltage and
frequency of the performance of the induction motor?
High voltage decreases both power factor and slip, but increases
torque. Low voltage has the opposite
effect. Increase in frequency increases
the power factor, but decreases the torque. The slip remains unchanged. Decrease in frequency has the opposite
effect.
Q What is in brief, the basis of operation of a
3 phase induction motor?
The revolving magnetic field which is produced when a 3-phase stator
winding is fed from a 3-phase supply.
Q. What factors determine the direction of
rotation of the motor ?
The phase sequence of the supply lines and the order in which these
lines are connected to the stator winding.
Q. How can the direction of rotation of the
motor be reversed ?
By transposing or changing over any two line leads.
Q. Why are induction motors called asynchronous
?
Because their rotors can never run with the synchronous speed.
Q. How does the slip vary with load ?
Greater the load, greater is the slip or slower is the rotor speed.
Q. What modifications would be necessary if a
motor is required to operate on voltage different from that for which it was
originally designed ?
The number of conductors per slot will have to be changed in the same
ratio as the change in voltage. If the voltage is doubled, the number of conductors
per slot will have to be doubled.
Q. Enumerate the possible reasons if a 3-phase
motor fails to start.
Any one of the following reasons could be responsible :
1. one or more fuses may be
blown.
2. voltage may be too low.
3. the starting load may be too
heavy.
4. worn bearings due to which
ihe armature may be touching field laminae, thus
introducing excessive
friction.
Q. A motor stops after starting i.e. it fails to
carry load. What could be the causes ?
Anyone of the following:
1. hot bearings, which increase
the load by excessive friction.
2. excessive tension on belt,
which causes the bearings lo heat. :
3. failure of short cut-out
switch.
4. single-phasing on the running
position of the starter.
Q. Which is the usual cause of blow-outs in
induction, motors ?
The commonest cause is single-phasing.
Q. What is meant by 'single-phasing' and what
are its causes ?
Single-phasing is meant the opening of one wire (or leg) of a
three-phase circuit thereupon the remaining leg at once becomes single-phase. When a
three-phase circuit functions normally, there are three distinct currents flowing in the
circuit. As is known, any two of these currents use the third wire as the return path i.e.
one of the three phases acts as a return path for the other two. Obviously, an open circuit in
one leg kills two of the phases and there will be only one current or phase working, even
though two wires are left intact. The remaining phase attempts to carry all the
load. The usual cause of single-phasing is, what is generally referred to as running fuse,
which is a fuse whose current carrying capacity is equal to the full-load current of the
motor connected in the circuit. This fuse will blow-out whenever there is overload (either
momentary or sustained on the motor.
Q. What happens if single-phasing occurs when
the motor is running ? And when it is stationary?
1. If already running and
carrying the half load or less, the motor will continue running as single-phase motor on the remaining single-phase supply, without damage
because half loads do not blow normal fuses.
2. If motor is very heavily
loaded, then it will stop under single-phasing since it can neither restart nor blow out the remaining fuses, the
burn-out is
very prompt.
A stationary motor will not start with one line broken. In fact, due to
heavy standstill current, it is likely to burn-out quickly unless immediately
disconnected.
Q. How can the motors be protected against
single-phasing ?
(i) By incorporating a combined overload" and single-phasing relay
in the controlgear.
(ii) by incorporating a phase-failure relay in the control gear. The
relay may be voltage or current-operated.
Q. Can a 3-phase motor be run on a single-phase
line ?
Yes, it can be. But a phase-splitter is essential.
Q. What is a meant by a phase-splitter ?
It is a device consisting of a number of capacitors so connected in,
the motor circuit it produces, from a single input wave, three output waves which differ
in phase from each other.
Q. What is the standard direction of rotation of
an induction motor ?
Counterclockwise, when looking from the front end i.e. non-driving end
of the motor.
Q. Can a wound-motor be reversed by transposing
any two leads-from the slip-ring
No. There is only one way of doing so i.e. by transposing any two line
leads.
Q. What is jogging ?
It means inching a motor i.e. make it move a little at a time by
constant starting and stopping.
Q. What is meant by plugging ?
It means stopping a motor by instantaneously reversing it till it
stops.
Q. What are the indications of winding faults in
an induction motor ?
Some of the indications are as under:
i. excessive and unbalanced
starting currents
ii. some peculiar noises and
(iii) overheating.
Q. What is ‘Crawling’ of Induction motor?
Squirrel cage motors sometimes exhibit a tendency stably at speeds as
low as 1/7th of their synchronous speed. This is known as crawling.
Q. What is ‘Cogging’?
This is also known as magnetic locking.
When the voltage is low, the motor does not start. This happens when the number of stator teeth
is equal to the number of rotor teeth and due to the magnetic locking, the
motor does not start. This can be overcome by making the number of rotor slots
prime to the number of stator slots.
"If you are not willing to risk the usual you will have to settle for the ordinary." --Jim Rohn
1 Comments
Legislation to legalize Massachusetts 온라인카지노 sports activities betting passed in August 2022, however isn't anticipated to fully launch until early 2023. Betting on in-state collegiate sports activities, both game outcomes and participant props, shall be prohibited. Betting on finish result} of an in-state faculty game will only be allowed if that staff is enjoying in} in a tournament comprising four or more teams. In addition, the casino offers loads of cost solutions to choose from|to select from} for an optimum gaming experience.
ReplyDeleteWe love to hear your comments on this article, so that we may better serve you in the future.